Harmonic distortion analysis in residential and industrial environments using the Fluke 1775 analyzer

Authors

DOI:

https://doi.org/10.59169/pentaciencias.v7i5.1637

Keywords:

Nonlinear loads; harmonic distortion; power quality; Fluke 1775; IEEE 519-2022

Abstract

The present study analyzed harmonic distortion levels in residential and industrial environments using the Fluke 1775 power quality analyzer, with the objective of providing a detailed description of each setting and verifying compliance with the limits established by the IEEE 519-2022 standard. The methodology involved conducting measurements over a period of seven days, with the analyzer's configuration adjusted to the characteristics of each environment. The collected data were processed using the Energy Analyze software, which allowed for the evaluation of distortion in both current and voltage. In the residential environment, harmonic distortion levels for both parameters were found to be within the normative limits. However, in the industrial environment, although the voltage remained within the allowed range, current levels showed significant distortion, exceeding the permitted limits by more than twice the established values. It is concluded that, while voltage quality was acceptable in both cases, the current harmonic distortion in the industrial environment represents a significant risk to the efficiency of the electrical system, highlighting the need to implement measures for harmonic mitigation.

Downloads

Download data is not yet available.

References

Achilie, C., y Molina, C. (2024). Análisis de la calidad de la energía orientado a distorsiones armónicas en el bloque de la universidad politécnica salesiana. Guayaquil: Universidad Politécnica Salesiana. https://dspace.ups.edu.ec/bitstream/123456789/27451/1/UPS-GT004985.pdf

Chere Ronquillo, E. E., y Quiroga Rendon, J. L. (25 de enero de 2025). Simulación de armónicos en redes trifásicas basada en la normativa ecuatoriana TDD y THD: caso de estudio en establecimiento recreativo. https://dspace.ups.edu.ec/bitstream/123456789/29971/1/UPS-GT006125.pdf

Desai, P. (02 de febrero de 2025). Estudio comparativo: Métodos, ideas y aplicaciones en la investigación. Blog Mind the Graph: https://mindthegraph.com/blog/es/comparison-study/

Fluke. (2024). Fluke-Direct.com. Fluke 1775 Three-Phase Power Quality Analyzer with current probes and WiFi/BLE adaptor, 8 kV: https://www.fluke-direct.com/product/fluke-1775-power-quality-analyzer

Hernández Sampieri, R., Collado, L., y Lucio, P. (s.f.). Universidades Aliat. http://online.aliat.edu.mx/adistancia/InvCuantitativa/LecturasS4/Hernandez_Sampieri_Cap._7_disenos_no_experimentales.pdf

Hernández Sampieri, R., Fernández Collado, C., y Baptista Lucio, M. d. (2014). METODOLOGÍA DE LA INVESTIGACIÓN. McGRAW-HILL Hill Education. https://doi.org/I978-1-4562-2396-0

Institute of Electrical and Electronics Engineers. (2022). 519-2022 - IEEE Standard for Harmonic Control in Electric Power Systems. IEEE. https://doi.org/10.1109/IEEESTD.2022.9848440

Pinyon, R. (abril de 2016). ARMÓNICOS: CAUSAS, EFECTOS Y MINIMIZACIÓN. SALICRU: https://www.salicru.com/files/pagina/72/278/jn004a00_whitepaper-armonics_.pdf

Rosero Sangucho, M. R., y Orizondo Martínez, R. A. (2023). REDUCCIÓN DE ARMÓNICOS CREADOS POR CORRIENTES NO SINUSOIDALES. Universidad Politécnica Salesiana. https://dspace.ups.edu.ec/bitstream/123456789/24833/1/TTS1297.pdf

Torres, G., y Sanches, J. M. (2020). Analisis de la calidad de la energia electrica servicio nacional de aprendizaje- SENA CEET. Bogotá: Universidad Distrial Francisco Jóse De Caldas. https://repository.udistrital.edu.co/server/api/core/bitstreams/0cd12bf8-70d9-4892-becd-e13984a07f21/content

Verma, V., Verma P., V., y Singh, H. (2019). THD Analysis of Non-Linear Loads. International Journal of Innovative Research in Electrical, Electronics, Instrumentation and Control Engineering, 33-38.

Zhang, X.-P., y Yan, Z. (2020). Energy Quality: A Definition. IEEE Open Access Journal of Power and Energy, 430-440. https://www.doi.org/%2010.1109/OAJPE.2020.3029767

Published

2025-10-10

How to Cite

Taco Cabrera , A. G. ., & Rodríguez Santillán, M. D. . (2025). Harmonic distortion analysis in residential and industrial environments using the Fluke 1775 analyzer . Revista Científica Arbitrada Multidisciplinaria PENTACIENCIAS - ISSN 2806-5794., 7(5), 31–46. https://doi.org/10.59169/pentaciencias.v7i5.1637

Issue

Section

Artículos originales